Installation Elgar CW-P Series
2-14 Operation Manual
To utilize remote sensing at the user's load, follow these steps:
1. Remove the protective cover from the terminal block.
2. Route the cables through the strain relief device located above the terminal block.
Twisted shielded leads for power and sense leads are recommended for the lowest
noise operation. If used, shields should be connected to a CW output terminal block
GND ground connector, as shown in Figure 3–9.
3. Disconnect localsense shorting jumpers. See Figure 3–9
4. Connect the sense leads as shown in Figure 3–9.
5. Reinstall the protective cover on the terminal block.
Figure 3–9 Sense Connections